Asia AMCA's testing laboratory is equipped with the latest, state-of-art equipment to perform Air and Sound Tests in accordance with AMCA International Test Standards and also comply with other International Standards, such as ISO 5801. Our laboratory obtained the Certification of Accreditation, ISO/IEC 17025: 2017, by the Department of Standards Malaysia.

Who to talk to:
Tan Tin Tin, Technical Director
Phone: +65 3157 6307
Email: tttan@asiaamca.org




Asia AMCA's Laboratory is able to test the following products:

FAN

Air Performance Test

Includes:
  • Development of Fan Curves
  • Measurement of Airflow, Pressure, Power & Efficiency
Test Standard:
  • AMCA Standard 210: Laboratory Methods of Testing Fans for Aerodynamic Performance Rating

Sound Test

Includes:
  • Inlet Sound Power
  • Outlet Sound Power
  • Total Sound Power
Test Standard:
  • AMCA Standard 300: Reverberant Room Method for Sound Testing of Fans

JET TUNNEL FAN

Includes:
  • Thrust Measurement
  • Sound Level
  • Vibration Velocity
Test Standard:
  • AMCA Standard 250: Laboratory Methods of Testing Airflow Measurement Stations for Performance Rating.




DAMPERS

Includes:
  • Pressure Drop
  • Leakage Test
Test Standard:
  • AMCA Standard 500-D: Laboratory Methods of Testing Dampers for Rating

AIRFLOW MEASURING STATION (AMS)

Includes:
  • Airflow Measurement
  • Airflow Resistance
Test Standard:
  • AMCA Standard 610: Laboratory Methods of Testing Jet Tunnel Fans for Performance.

The laboratory capabilities of the Asia AMCA Lab in Johor, Malaysia

AMCA 210Small ChamberLarge Chamber
Figure 12 Max Outlet Area - Perpendicular Rotation 0.252 m2 (2.715 ft2) 2.20 m2 (23.67 ft2)

Figure 12 Max Outlet Area - Parallel Rotation
(Vane Axial Fans Only)

0.142 m2 (1.527 ft2)

1.24 m2 (13.34 ft2)

Figure 12 Max Outlet Area - Parallel Rotation 0.091 m2 (0.977 ft2) 0.794 m2 (8.54 ft2)
Figure 15 Max Inlet Area - Any Rotation 0.454 m2 (4.886 ft2) 4.89 m2 (52.62 ft2)
Max Airflow at 0 in. wg 4.54 m3/s (9,620 cfm) 39.5 m3/s (68,000 cfm (Figure 12))
48.1 m3/s (88,000 cfm (Figure 15))
Max Static Pressure 2500 Pa (10 in. wg) 8000 Pa (32 in. wg)
Max Brake Horsepower 11 kW (15 HP) @ 2900 RPM
37 kW (50HP) @ 1500 RPM
Max Dynamometer Speed 1500 RPM @ 37 kW (50HP)
2900 RPM @ all others
Electric Motor (50 Hz) 65 Amps, 440 Volts
AMCA 500Small ChamberLarge Chamber
Duct Sizes Round (mm) 305, 610 914
Duct Sizes Rectangle (mm) 305x305
610x610
914x914
305x1220
Figure 5.3 Max Free Area 0.372 m2 (4 ft2) 0.837 m2 (9 ft2)
Figure 5.4 Max Free Area 0.151 m2 (1.63 ft2) 1.323 m2 (14.23 ft2)
Figure 5.5 Max Free Area 0.757 m2 (8.14 ft2) 8.15 m2 (87.70 ft2)
AMCA 300
Max volume of Test Unit Duct Work 14.4 m3 (509 ft3)
Frequency 63 125 250 500 1000 2000 4000 8000 LwA
Approx Min Fan Lw
Reverb Room (dB)
66 53 47 41 34 27 32 33 46

Air Movement and Control Association International, Inc.